DESCRIPTION

  • DSP controlled next generation technology

  • Grid-tied & off grid operation selectable

  • True Bi-directional hybrid solar inverter

  • Rating available 1000VA to 5000VA

  • AC-DC galvanic isolation for shock proof protection

  • Inbuilt solar MPPT & Grid batt. Charger

  • Highly efficient than conventional x-mer version

  • User-friendly LCD & LED Display

  • Light weight, wall mounting design

  • Field tested and proven design

  • Mobile connectivity via Wi-Fi / Bluetooth (optional)

technology greeny solar hybrid off & on grid

Technical Specification of Greeny Solar Hybrid-X on and off Grid Inverter

MODEL GREENY SHXI1000 GREENY SHXI2000 GREENY SHXI3000 GREENY SHXI5000
PV INPUT
MAXIMUM PV CAPACITY 1000W 2000W 3000W 5000W
MAXIMUM DC VOLTAGE 450V
MINIMUM DC VOLTAGE 70V
MPPT VOLTAGE RANGE 125-350V
NO. OF MPPT TRACKER 1
MPPT TRACKER TYPE INTER-LIVED BOOST CONVERTER WITH MPPT
MPPT EFFICIENCY 98%
OUTPUT AC
AC NOMINAL POWER 1000W 2000W 3000W 4000W
NOMINAL AC VOLTAGE; RANGE;FREQUENCY 230V;180-265V;50Hz;45-55Hz
INVERTER EFFICIENCY 97%
THD <3
POWER FACTOR 100%
DISPLACEMENT POWER FACTOR 0.8 LEADING TO 0.8 LAGGING
BATTERY
BATTERY TYPE LEAD-ACID BATTERY/LITHIUM BATTERY
NOMINAL BATTERY VOLTAGE 24V DC 48V DC 48V DC 48V DC
LOW BATTERY ALARM 21.50V DC ± 0.2% 43.00V DC ± 0.2% 43.00V DC ± 0.2% 43.00V DC ± 0.2%
LOW BATTERY TRIP 21.00V DC ± 0.2% 42.00V DC ± 0.2% 42.00V DC ± 0.2% 42.00V DC ± 0.2%
GENERAL
OPERATING TEMPERATURE RANGE 0-55°C
RELATIVE HUMIDITY 0-95%
COOLING CONCEPT FORCED AIRFLOW WITH FAN(DC FAN)
NOISE EMISSION(TYPICAL) <40dB
TOPOLOGY TRANSFORMER-LESS
EMC STANDARD IEC61000-6-1/2/3
ENCLOSURE TYPE WALL-MOUNTING TYPE (Indoor)
DIMENSIONS (L*W*S) 255X250X100mm 385X315X110mm 500X400X110mm 500X400X110mm
WEIGHT 3.5Kg 8.5Kg 15Kg 25Kg
DISPLAY PARAMETERS LED:BYPASS MODE,GRID BATTERY CHARGING, BACKUP MODE, LOW BATTERY, OVERLOAD
LCD:PV VOLTAGE, PV POWER, BATTERY VOLTAGE AND BATTERY STATUS, PV CHARGER STATUS AND ALL FAULTS